@nickfost_ 3/4" EMT. Strap every 10'. Not wet location use set screw connectors. Going to need a bonding bushing at the panel and enclosure. Pigtail or ground screw for metal boxes.
Factor cost of conduit bender and reamer.
@nickfost_ If you're running NM-B you'll need 4/3. Use THHN and conduit and you can go with 6
awg for your conductors and 8awg for your ground.
The drop in voltage for the 6awg at that distance is ~2.25%.
Make sure your breakers at 75*C rated for the 6awg run.