Recent electrification work:
"Getting things back on track"
This house in RVA used to be all-electric, but the folks who flipped it had fossil gas installed, along w/ a new furnace!🤦♂️
The new owners were *not* on board + had us install new heat pumps. Gas meter removal next..
@JesseTayRiver@ScottFarbman@jbsties Largely agree...though I suspect it's easier to fake a manometer pic than to fake a computer/app-controlled multi-point test.
In this case, we're required to do the multi-point test for the HERS rating...so we didn't also do a single-point test.
While delivering superior comfort, nearly silent indoor/outdoor operation, + more than 3x improved air filtration, this heat pump system our squad recently installed is an energy efficiency beast, compared to the straight cooling system it replaced.
1/4
@EfficiencyLast ...setup thermostat for 2-stage airflow operation (400/800cfm)...system runs most of the time in stage 1, so outdoor unit ramps down as needed.
@EfficiencyLast Likely small reductions in duct leakage (not measured), but no other changes in the envelope.
Big reduction in air handler fan energy.
Big reduction in outdoor unit energy from: more efficient outdoor unit, limit outdoor unit to nominal 2-ton output...
@energysmartwv Yes...and reduced airflow via lower capacity equipment and staging on the thermostat. The new air handler is ~115W at 800cfm (stage 2), but only ~30W at 400cfm (stage 1). System runs 80%+ of the time in stage 1.
@energysmartwv Also note that ~20% of overall savings are from indoor air side alone. Very efficient, variable speed air handler + reduced airflow (was ~1,200cfm nominal...now typically operates at 400cfm w/ boost to 800cfm as need)...along w/ simple but important duct + filter improvements.
@energysmartwv 60% energy use reduction (not 70%).
We wouldn't be surprised if there was something wrong with the old system, but detailed diagnostics of the old one was outside of our scope. At the same time, it was able to keep the house cool the previous year.
@energysmartwv@neil_comparetto @JohnSemmelhack That work was done by others in past years...not sure why they insulated the floor, rather than the foundation walls.
Even more impressive, the new air handler used about the same amount of energy in July as the old, cooling-only model used during each of the Fall/Winter months!....when it was doing *NOTHING*, but was powered on.
4/4
In particular, the new air handler + nearby ductwork we installed are absolute winners, saving 86% of the fan energy compared to the old system, despite increasing filter performance from MERV-4 to MERV-13.
3/4